GWS Pressure Tank Pre-charge settings
Changing transport regulations in some parts of the world have required that some pressure tanks be transported with lower than previous air pre-charge.
As was always the case, and especially now with pressure tanks being used in a greater variety of applications, it is necessary to correctly set the pre-charge air pressure to match the installation and to not void warranty.
- Pressure switch controlled pumps with differential pressure set at 140 kPa (20 psi), pre-charge the tank to 20 kPa (3 psi) below the cut in pressure.
- For pumps controlled by pressure switches with higher differential pressures, electronic controls or variable speed controls, pre-charge the tank to 65% of the maximum system pressure.
- Pressure tanks installed on mains pressure, pre-charge should be set at the mains pressure.
- For hot water expansion, pre-charge should be set at the mains pressure.